Sprinkler, nickel plated, 68°C, straight
Sprinkler: 1/2", nickel-plated, 68°C, K=80.6, pendent, straight.
Pendent sprinklers are installed below the pipes, while upright sprinklers are installed above the pipes.
The MBK Series, with a 5.6 K-factor (K=80), includes both upright and pendent sprinklers. These standard response, standard coverage, decorative 5 mm glass bulb-type spray sprinklers are designed for use in light, ordinary, or extra hazard commercial occupancies such as banks, hotels, shopping malls, factories, refineries, and chemical plants.
Characteristics:
| Property | Details |
|---|---|
| Material | Brass and chrome plating, with plastic protection |
| Temperature | 68℃ with 5mm glass bulb |
| Thread | 1/2" |
| K | 80 |
| Type | Pendent |
| Respond | Standard respond |
| Rated Working Pressure | 12 bars (1.2 MPa) |
| Air Proof Test Pressure | 24 bars (2.4 MPa) |
| Strength Test Pressure | 30 bars (3 MPa) |
| Weight | ~53 g |